FPLR SHIELDED

 

                       FIRE POWER LIMITED RISER

 

 

 

TEMPERATURE RATING: 60°C
COPPER TYPE: SOLID BARE COPPER
CHARACTERISTICS: 2 OR MORE CONDUCTORS INSULATED WITH FIRE RETARDENT PVC, TWISTED FOR MAXIMUM FLEXIBILITY,SHIELDED WITH ALUM. MYLAR FOIL AND A STRANDED TINNED COPPER DRAIN, AND JACKETED WITH FIRE RET. PVC.  MEETS NEC ARTICLE 760 AND CALIFORNIA FIRE MARSHALL REQUIREMENTS
APPLICATIONS: FIRE DETECTION

 

PART # AWG # COND INSULATION THICKNESS JACKET THICKNESS NOMINAL O.D.
460422R 22 4 .006 .014 .121
460218R 18 2 .006 .014 .146
460418R 18 4 .006 .014 .157
460618R 18 6 .006 .014 .179
460216R 16 2 .006 .014 .171
460416R 16 4 .006 .014 .183
460214R 14 2 .006 .014 .199
460414R 14 4 .006 .014 .214
460212R 12 2 .006 .014 .256

**COLOR CHART # 2

** STANDARD JACKET COLOR-RED